SZR-280-12V,
FUNCTIONS
* Simultaneous control of two power lines
* Measured values TrueRMS
* Galvanic separation of measuring inputs supply lines
* Contactors control
* Support for an emergency generator exhaust
* Working in automatic mode, with the possibility of determining the priority line
* Power Dump is achieved through separation of the receiving line into two parts,
with possibility to freely define of the power dump cases
* An independent determination of voltage range for each of the line for which line
qualified as good, and the voltage hysteresis determination of the line qualifications
* The definition of eligibility as a good line, and the time of qualification as a bad line.
* Accelerated classification as a bad line in case of total loss of voltage on the line
* The definition of time-controlled switching on and off contactors
* Ability to connect to an external safety circuit lock the controller work
* Configure the driver through a PC using a dedicated application
* Events registration with the possibility of export of the registration file to your PC
Availability date:
Controller power supply - power supply voltage | 12 V AC/DC |
Controlled lines | 3 x 400 V + N (four-wire) |
The number of controlled lines | 2 |
Measured input voltages - rated voltage | 230 V |
Measured input voltages - measuring range | 80÷300 V |
Measured input voltages - frequency | 45÷50 Hz |
Measured input voltages - accuracy | 1% of full scale + 1 digit |
Relay outputs typ | contacts 5 x [1xNO] |
Relay outputs, load capacity | 8:00 AM |
Terminal | pluggable terminal blocks 2,5 mm² |
Tightening torque | 0,4 Nm |
Power consumption | 4 W |
Working temperature | 10÷40ºC |
Dimensions | 100 x 75 x 110 mm |
Assembly | on rail 35 mm |
Ingress Protection Marking | IP20 |